CVE-2018-16556 Denial of service in SIMATIC S7-400 CPU 412-1 DP V7

High 7.5 Published Updated

Remote attackers can cause denial of service on Siemens SIMATIC S7-400 CPUs by sending specially crafted packets, requiring manual reboot to restore operation.

Exploited in the wild
Not known
Login needed
Not needed
Attackable
Over the internet
Victim action needed
Not needed
Fix
None listed

What is CVE-2018-16556?

CVE-2018-16556 is a high-severity denial of service vulnerability in Siemens SIMATIC S7-400 CPU 412-1 DP V7, published on 13 Dec 2018. An attacker can exploit it over the internet without logging in, with no action from the victim.

Official description

A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Specially crafted packets sent to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected devices to go into defect mode. Manual reboot is required to resume normal operation. Successful exploitation requires an attacker to be able to send specially crafted packets to port 102/tcp via Ethernet interface, via PROFIBUS or Multi Point Interfaces (MPI). No user interaction and no user privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.

Weakness: CWE-20

Which versions are affected by CVE-2018-16556?

It affects 5 products.

Products include Siemens Simatic S7-400 Firmware, Siemens Simatic S7-400 Pn\/Dp V7 Firmware, Siemens Simatic S7-400h Firmware, Siemens Simatic S7-400h V6 Firmware, Siemens Simatic S7-410 Firmware.

How do I fix CVE-2018-16556?

No fix has been published for CVE-2018-16556 yet. Limit exposure of the affected software until one is available.

Upgrade, then put limits on request size, rate and nesting depth so one client cannot exhaust the service. More about Denial of service.

Is CVE-2018-16556 being exploited?

There is no known exploitation of CVE-2018-16556 in the wild and no public exploit code.