{"answers":{"affected":"It affects 2 products.","exploited":"There is no known exploitation of CVE-2020-15795 in the wild and no public exploit code.","fix":"No fix has been published for CVE-2020-15795 yet. Limit exposure of the affected software until one is available.","what":"CVE-2020-15795 is a high-severity memory corruption vulnerability in Siemens APOGEE PXC Compact (BACnet), published on 22 Apr 2021. An attacker can exploit it over the internet without logging in, with no action from the victim."},"fix_prompt":"Check this codebase for CVE-2020-15795 and fix it if it is affected.\n\nWhat it is: CVE-2020-15795 is a high-severity memory corruption vulnerability in Siemens APOGEE PXC Compact (BACnet), published on 22 Apr 2021. An attacker can exploit it over the internet without logging in, with no action from the victim.\nExploitation: There is no known exploitation of CVE-2020-15795 in the wild and no public exploit code.\n\nAffected product: Siemens APOGEE PXC Compact (BACnet). No package-level version data is available, so check the vendor advisory linked from the reference page.\n\nTask:\n1. Search the dependency manifests and lockfiles (for example package.json, package-lock.json, requirements.txt, poetry.lock, uv.lock, pom.xml, build.gradle, go.mod, Cargo.lock, Gemfile.lock) and any Dockerfiles for the affected packages, including transitive dependencies.\n2. If an affected version is in use, upgrade it to the fixed version for its release line with the project's package manager, so the lockfile is regenerated. Prefer the smallest upgrade that fixes it.\n3. If there is no fix, or the upgrade would break the build, do not guess: explain the risk and the safest workaround instead.\n4. Run the tests and summarise what changed and why.\n5. If nothing in the project is affected, say so and change nothing.\n\nReference: https://insights.sbomify.com/CVE-2020-15795/ (Markdown: https://insights.sbomify.com/CVE-2020-15795/index.md)","id":"CVE-2020-15795","markdown":"https://insights.sbomify.com/CVE-2020-15795/index.md","name":"CVE-2020-15795","record":{"aliases":["GHSA-cw98-4v34-2rc8"],"analysis":{"component_type":"ics_ot","fix_type":"upgrade","impacts":["code_execution","denial_of_service"],"network_reachable":"yes","non_default_config":false,"product_category":"Siemens building automation","requires_auth":"none","summary":"A memory corruption vulnerability in Siemens building automation systems allows attackers to execute code or cause denial of service via malformed DNS responses.","user_interaction":"not_required","vuln_class":"memory_corruption"},"analysis_generated_by":"qwen3.8-flash-next","assigner":"siemens","cpe":[{"product":"nucleus_net","vendor":"siemens"},{"product":"nucleus_source_code","vendor":"siemens"}],"cvss":{"score":8.1,"severity":"high","source":"cna","vector":"CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C","version":"3.1"},"cwes":[{"id":"CWE-787","name":"Out-of-bounds Write"}],"description":"A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions \u003c V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions \u003c V2.8.20), APOGEE PXC Modular (BACnet) (All versions \u003c V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions \u003c V2.8.20), Nucleus NET (All versions \u003c V5.2), Nucleus Source Code (Versions including affected DNS modules), TALON TC Compact (BACnet) (All versions \u003c V3.5.5), TALON TC Modular (BACnet) (All versions \u003c V3.5.5). The DNS domain name label parsing functionality does not properly validate the names in DNS-responses. The parsing of malformed responses could result in a write past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to execute code in the context of the current process or cause a denial-of-service condition.","ecosystems":[],"exploits":{"exploitdb":0,"first_seen":null,"github_poc":0,"max_poc_stars":null,"metasploit":0,"nuclei":0,"refs":[],"tier":"none_known"},"has_fix":null,"headline":"Memory corruption in APOGEE PXC Compact (BACnet)","id":"CVE-2020-15795","indexable":true,"kev":null,"kind":"cve","links":{"ecosystem":null,"product":null,"products":[],"type":"memory_corruption","year":"2020"},"n_packages":0,"n_references":2,"next":{"headline":"Denial of service in SIMATIC ET 200SP Open Controller (incl. SIPLUS variants)","id":"CVE-2020-15796"},"packages":[],"prev":{"headline":"Information disclosure in Desigo Insight","id":"CVE-2020-15794"},"products":["APOGEE PXC Compact (BACnet)","APOGEE PXC Compact (P2 Ethernet)","APOGEE PXC Modular (BACnet)","APOGEE PXC Modular (P2 Ethernet)","Nucleus NET","Nucleus Source Code","TALON TC Compact (BACnet)","TALON TC Modular (BACnet)"],"published":"2021-04-22","related":[{"cvss_score":8.1,"headline":"Memory corruption in APOGEE PXC Compact (BACnet)","id":"CVE-2020-27009","kev_date_added":null,"published":"2021-04-22"},{"cvss_score":6.5,"headline":"Memory corruption in APOGEE PXC Compact (BACnet)","id":"CVE-2020-27736","kev_date_added":null,"published":"2021-04-22"},{"cvss_score":6.5,"headline":"Memory corruption in APOGEE PXC Compact (BACnet)","id":"CVE-2020-27737","kev_date_added":null,"published":"2021-04-22"},{"cvss_score":6.5,"headline":"Memory corruption in APOGEE PXC Compact (BACnet)","id":"CVE-2020-27738","kev_date_added":null,"published":"2021-04-22"},{"cvss_score":5.3,"headline":"Other in APOGEE PXC Compact (BACnet)","id":"CVE-2021-25677","kev_date_added":null,"published":"2021-04-22"},{"cvss_score":5.3,"headline":"Other in Nucleus NET","id":"CVE-2021-27393","kev_date_added":null,"published":"2021-04-22"}],"sources":[{"class":"attribution","licence":"CVE Terms of Use (MITRE)","name":"CVE List","prefix":"CVE"},{"class":"attribution","licence":"US public information, NVD API terms","name":"NVD"},{"class":"attribution","licence":"CWE Terms of Use","name":"CWE (MITRE)"},{"class":"attribution","licence":"FIRST CVSS licence","name":"CVSS (FIRST)"}],"ssvc":{"automatable":null,"exploitation":null,"technical_impact":null},"state":"PUBLISHED","updated":"2024-08-04","vendors":["Siemens"]},"summary":"A memory corruption vulnerability in Siemens building automation systems allows attackers to execute code or cause denial of service via malformed DNS responses.","url":"https://insights.sbomify.com/CVE-2020-15795/"}