CVE-2022-33175 Information disclosure in n/a

Critical 9.8 Published Updated

Attackers can steal administrator session IDs via an insecure API, enabling unauthorized access to read passwords and reconfigure the device.

Exploited in the wild
Not known
Login needed
Not needed
Attackable
Over the internet
Victim action needed
Not needed
Fix
None listed

What is CVE-2022-33175?

CVE-2022-33175 is a critical vulnerability in n/a, published on 13 Jun 2022. An attacker can exploit it over the internet without logging in, with no action from the victim.

Official description

Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 have an insecure permissions setting on the user.token field that is accessible to everyone through the /cgi/get_param.cgi HTTP API. This leads to disclosing active session ids of currently logged-in administrators. The session id can then be reused to act as the administrator, allowing reading of the cleartext password, or reconfiguring the device.

Weakness: CWE-732

Which versions are affected by CVE-2022-33175?

It affects 7 products.

Products include Powertekpdus Basic Pdu Firmware, Powertekpdus Piml Pdu Firmware, Powertekpdus Pm Pdu Firmware, Powertekpdus Smart Pim Firmware, Powertekpdus Smart Pom Firmware, Powertekpdus Smart Poms Firmware and 1 more.

How do I fix CVE-2022-33175?

No fix has been published for CVE-2022-33175 yet. Limit exposure of the affected software until one is available.

Is CVE-2022-33175 being exploited?

There is no known exploitation of CVE-2022-33175 in the wild and no public exploit code.

Sources

Also known as GHSA-x3x3-7q8c-m397.

Is CVE-2022-33175 in your software?

Upload an SBOM and sbomify checks it against every vulnerability here, every day.

Check your SBOMs for free