CVE-2022-40176 Command injection in Desigo PXM30-1
A remote low-privileged attacker can execute arbitrary system commands with root privileges by restoring a crafted package on Siemens Desigo PXM devices.
- Exploited in the wild
- Not known
- Login needed
- Any signed-in user
- Attackable
- Over the internet
- Victim action needed
- A user has to click or open something
- Fix
- None listed
What is CVE-2022-40176?
CVE-2022-40176 is a high-severity command injection vulnerability in Siemens Desigo PXM30-1, published on 11 Oct 2022. Any signed-in user can exploit it over the network, and only if a user opens a file or follows a link.
Official description
A vulnerability has been identified in Desigo PXM30-1 (All versions < V02.20.126.11-41), Desigo PXM30.E (All versions < V02.20.126.11-41), Desigo PXM40-1 (All versions < V02.20.126.11-41), Desigo PXM40.E (All versions < V02.20.126.11-41), Desigo PXM50-1 (All versions < V02.20.126.11-41), Desigo PXM50.E (All versions < V02.20.126.11-41), PXG3.W100-1 (All versions < V02.20.126.11-37), PXG3.W100-2 (All versions < V02.20.126.11-41), PXG3.W200-1 (All versions < V02.20.126.11-37), PXG3.W200-2 (All versions < V02.20.126.11-41). There exists an Improper Neutralization of Special Elements used in an OS Command with root privileges during a restore operation due to the missing validation of the names of files included in the input package. By restoring a specifically crafted package, a remote low-privileged attacker can execute arbitrary system commands with root privileges on the device, leading to a full compromise.
Weakness: CWE-78
Which versions are affected by CVE-2022-40176?
It affects 10 products.
Products include Siemens Desigo Pxm30-1 Firmware, Siemens Desigo Pxm30.e Firmware, Siemens Desigo Pxm40-1 Firmware, Siemens Desigo Pxm40.e Firmware, Siemens Desigo Pxm50-1 Firmware, Siemens Desigo Pxm50.e Firmware and 4 more.
How do I fix CVE-2022-40176?
No fix has been published for CVE-2022-40176 yet. Limit exposure of the affected software until one is available.
Upgrade, and pass arguments to programs as a list instead of through a shell. More about Command injection.
Is CVE-2022-40176 being exploited?
There is no known exploitation of CVE-2022-40176 in the wild and no public exploit code.
Other vulnerabilities in Siemens Desigo PXM30-1
Sources
Also known as GHSA-f4pq-rpfq-ggjx.