CVE-2022-45044 Denial of service in SIPROTEC 5 6MD84 (CP300)
Attackers can cause a denial of service in Siemens SIPROTEC 5 devices by exploiting a resource exhaustion vulnerability.
- Exploited in the wild
- Not known
- Login needed
- Not needed
- Attackable
- Over the internet
- Victim action needed
- Not needed
- Fix
- None listed
What is CVE-2022-45044?
CVE-2022-45044 is a medium-severity denial of service vulnerability in Siemens SIPROTEC 5 6MD84 (CP300), published on 13 Dec 2022. An attacker can exploit it over the internet without logging in, with no action from the victim.
Official description
A vulnerability has been identified in SIPROTEC 5 6MD84 (CP300) (All versions < V9.50), SIPROTEC 5 6MD85 (CP200) (All versions), SIPROTEC 5 6MD85 (CP300) (All versions < V9.50), SIPROTEC 5 6MD86 (CP200) (All versions), SIPROTEC 5 6MD86 (CP300) (All versions < V9.50), SIPROTEC 5 6MD89 (CP300) (All versions < V9.64), SIPROTEC 5 6MU85 (CP300) (All versions < V9.50), SIPROTEC 5 7KE85 (CP200) (All versions), SIPROTEC 5 7KE85 (CP300) (All versions < V9.64), SIPROTEC 5 7SA82 (CP100) (All versions < V8.90), SIPROTEC 5 7SA82 (CP150) (All versions < V9.50), SIPROTEC 5 7SA84 (CP200) (All versions), SIPROTEC 5 7SA86 (CP200) (All versions), SIPROTEC 5 7SA86 (CP300) (All versions < V9.50), SIPROTEC 5 7SA87 (CP200) (All versions), SIPROTEC 5 7SA87 (CP300) (All versions < V9.50), SIPROTEC 5 7SD82 (CP100) (All versions < V8.90), SIPROTEC 5 7SD82 (CP150) (All versions < V9.50), SIPROTEC 5 7SD84 (CP200) (All versions), SIPROTEC 5 7SD86 (CP200) (All versions), SIPROTEC 5 7SD86 (CP300) (All versions < V9.50), SIPROTEC 5 7SD87 (CP200) (All versions), SIPROTEC 5 7SD87 (CP300) (All versions < V9.50), SIPROTEC 5 7SJ81 (CP100) (All versions < V8.89), SIPROTEC 5 7SJ81 (CP150) (All versions < V9.50), SIPROTEC 5 7SJ82 (CP100) (All versions < V8.89), SIPROTEC 5 7SJ82 (CP150) (All versions < V9.50), SIPROTEC 5 7SJ85 (CP200) (All versions), SIPROTEC 5 7SJ85 (CP300) (All versions < V9.50), SIPROTEC 5 7SJ86 (CP200) (All versions), SIPROTEC 5 7SJ86 (CP300) (All versions < V9.50), SIPROTEC 5 7SK82 (CP100) (All versions < V8.89), SIPROTEC 5 7SK82 (CP150) (All versions < V9.50), SIPROTEC 5 7SK85 (CP200) (All versions), SIPROTEC 5 7SK85 (CP300) (All versions < V9.50), SIPROTEC 5 7SL82 (CP100) (All versions < V8.90), SIPROTEC 5 7SL82 (CP150) (All versions < V9.50), SIPROTEC 5 7SL86 (CP200) (All versions), SIPROTEC 5 7SL86 (CP300) (All versions < V9.50), SIPROTEC 5 7SL87 (CP200) (All versions), SIPROTEC 5 7SL87 (CP300) (All versions < V9.50), SIPROTEC 5 7SS85 (CP200) (All versions), SIPROTEC 5 7SS85 (CP300) (All versions < V9.50), SIPROTEC 5 7ST85 (CP200) (All versions), SIPROTEC 5 7ST85 (CP300) (All versions < V9.64), SIPROTEC 5 7ST86 (CP300) (All versions < V9.64), SIPROTEC 5 7SX82 (CP150) (All versions < V9.50), SIPROTEC 5 7SX85 (CP300) (All versions < V9.50), SIPROTEC 5 7UM85 (CP300) (All versions < V9.50), SIPROTEC 5 7UT82 (CP100) (All versions < V8.90), SIPROTEC 5 7UT82 (CP150) (All versions < V9.50), SIPROTEC 5 7UT85 (CP200) (All versions), SIPROTEC 5 7UT85 (CP300) (All versions < V9.50), SIPROTEC 5 7UT86 (CP200) (All versions), SIPROTEC 5 7UT86 (CP300) (All versions < V9.50), SIPROTEC 5 7UT87 (CP200) (All versions), SIPROTEC 5 7UT87 (CP300) (All versions < V9.50), SIPROTEC 5 7VE85 (CP300) (All versions < V9.50), SIPROTEC 5 7VK87 (CP200) (All versions), SIPROTEC 5 7VK87 (CP300) (All versions < V9.50), SIPROTEC 5 7VU85 (CP300) (All versions < V9.50), SIPROTEC 5 Communication Module ETH-BA-2EL (Rev.1) (All versions installed on CP200 devices), SIPROTEC 5 Communication Module ETH-BA-2EL (Rev.1) (All versions < V9.50 installed on CP150 and CP300 devices), SIPROTEC 5 Communication Module ETH-BA-2EL (Rev.1) (All versions < V8.89 installed on CP100 devices), SIPROTEC 5 Communication Module ETH-BB-2FO (Rev. 1) (All versions installed on CP200 devices), SIPROTEC 5 Communication Module ETH-BB-2FO (Rev. 1) (All versions < V9.50 installed on CP150 and CP300 devices), SIPROTEC 5 Communication Module ETH-BB-2FO (Rev. 1) (All versions < V8.89 installed on CP100 devices), SIPROTEC 5 Communication Module ETH-BD-2FO (All versions < V9.50), SIPROTEC 5 Compact 7SX800 (CP050) (All versions < V9.50). Affected devices do not properly restrict secure client-initiated renegotiations within the SSL and TLS protocols. This could allow an attacker to create a denial of service condition on the ports 443/tcp and 4443/tcp for the duration of the attack.
Weakness: CWE-400
Which versions are affected by CVE-2022-45044?
It affects 34 products.
Products include Siemens Siprotec 5 6md85 Firmware, Siemens Siprotec 5 6md86 Firmware, Siemens Siprotec 5 6md89 Firmware, Siemens Siprotec 5 6mu85 Firmware, Siemens Siprotec 5 7ke85 Firmware, Siemens Siprotec 5 7sa82 Firmware and 28 more.
How do I fix CVE-2022-45044?
No fix has been published for CVE-2022-45044 yet. Limit exposure of the affected software until one is available.
Upgrade, then put limits on request size, rate and nesting depth so one client cannot exhaust the service. More about Denial of service.
Is CVE-2022-45044 being exploited?
There is no known exploitation of CVE-2022-45044 in the wild and no public exploit code.
Other vulnerabilities in Siemens SIPROTEC 5 6MD84 (CP300)
Sources
Also known as GHSA-q2fm-89c2-x6c2.