{"answers":{"affected":"","exploited":"There is no known exploitation of CVE-2024-12169 in the wild and no public exploit code.","fix":"No fix has been published for CVE-2024-12169 yet. Limit exposure of the affected software until one is available.","what":"CVE-2024-12169 is a high-severity denial of service vulnerability in Hitachi Energy RTU500, published on 25 Mar 2025. An attacker can exploit it over the internet without logging in, with no action from the victim."},"fix_prompt":"Check this codebase for CVE-2024-12169 and fix it if it is affected.\n\nWhat it is: CVE-2024-12169 is a high-severity denial of service vulnerability in Hitachi Energy RTU500, published on 25 Mar 2025. An attacker can exploit it over the internet without logging in, with no action from the victim.\nExploitation: There is no known exploitation of CVE-2024-12169 in the wild and no public exploit code.\n\nAffected product: Hitachi Energy RTU500. No package-level version data is available, so check the vendor advisory linked from the reference page.\n\nTask:\n1. Search the dependency manifests and lockfiles (for example package.json, package-lock.json, requirements.txt, poetry.lock, uv.lock, pom.xml, build.gradle, go.mod, Cargo.lock, Gemfile.lock) and any Dockerfiles for the affected packages, including transitive dependencies.\n2. If an affected version is in use, upgrade it to the fixed version for its release line with the project's package manager, so the lockfile is regenerated. Prefer the smallest upgrade that fixes it.\n3. If there is no fix, or the upgrade would break the build, do not guess: explain the risk and the safest workaround instead.\n4. Run the tests and summarise what changed and why.\n5. If nothing in the project is affected, say so and change nothing.\n\nReference: https://insights.sbomify.com/CVE-2024-12169/ (Markdown: https://insights.sbomify.com/CVE-2024-12169/index.md)","id":"CVE-2024-12169","markdown":"https://insights.sbomify.com/CVE-2024-12169/index.md","name":"CVE-2024-12169","record":{"aliases":["GHSA-6pf8-q335-vxv9"],"analysis":{"component_type":"ics_ot","fix_type":"patch","impacts":["denial_of_service"],"network_reachable":"yes","non_default_config":true,"product_category":"RTU500 ICS controller","requires_auth":"none","summary":"An attacker can restart the RTU500 controlled station via a specific attack sequence when secure communication is enabled, causing denial of service.","user_interaction":"not_required","vuln_class":"denial_of_service"},"analysis_generated_by":"qwen3.8-flash-next","assigner":"Hitachi Energy","cpe":[],"cvss":{"score":8.7,"severity":"high","source":"cna","vector":"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/R:A","version":"4.0"},"cwes":[],"description":"A vulnerability exists in RTU500 IEC 60870-5-104 controlled station functionality and IEC 61850 functionality, that allows an attacker performing a specific attack sequence to restart the affected CMU. This vulnerability only applies, if secure communication using IEC 62351-3 (TLS) is enabled.","ecosystems":[],"exploits":{"exploitdb":0,"first_seen":null,"github_poc":0,"max_poc_stars":null,"metasploit":0,"nuclei":0,"refs":[],"tier":"none_known"},"has_fix":null,"headline":"Denial of service in RTU500","id":"CVE-2024-12169","indexable":true,"kev":null,"kind":"cve","links":{"ecosystem":null,"product":null,"products":[],"type":"denial_of_service","year":"2024"},"n_packages":0,"n_references":1,"next":{"headline":"ViewMedica Embed \u003c= 1.4.15 - Cross-Site Request Forgery to SQL Injection","id":"CVE-2024-12170"},"packages":[],"prev":{"headline":"DLL Hijacking in Yandex Telemost","id":"CVE-2024-12168"},"products":["RTU500"],"published":"2025-03-25","related":[],"sources":[{"class":"attribution","licence":"CVE Terms of Use (MITRE)","name":"CVE List","prefix":"CVE"},{"class":"attribution","licence":"FIRST CVSS licence","name":"CVSS (FIRST)"}],"ssvc":{"automatable":"no","exploitation":"none","technical_impact":"partial"},"state":"PUBLISHED","updated":"2025-03-25","vendors":["Hitachi Energy"]},"summary":"An attacker can restart the RTU500 controlled station via a specific attack sequence when secure communication is enabled, causing denial of service.","url":"https://insights.sbomify.com/CVE-2024-12169/"}