CVE-2024-41978 Information disclosure in RUGGEDCOM RM1224 LTE(4G) EU

High 7.1 Published Updated

An authenticated attacker can read sensitive 2FA token generation data from log files to forge tokens and take over other user accounts.

Exploited in the wild
Not known
Login needed
Any signed-in user
Attackable
Over the internet
Victim action needed
Not needed
Fix
None listed

What is CVE-2024-41978?

CVE-2024-41978 is a high-severity vulnerability in Siemens RUGGEDCOM RM1224 LTE(4G) EU, published on 13 Aug 2024. Any signed-in user can exploit it over the network, with no action from the victim.

Official description

A vulnerability has been identified in RUGGEDCOM RM1224 LTE(4G) EU (6GK6108-4AM00-2BA2) (All versions < V8.1), RUGGEDCOM RM1224 LTE(4G) NAM (6GK6108-4AM00-2DA2) (All versions < V8.1), SCALANCE M804PB (6GK5804-0AP00-2AA2) (All versions < V8.1), SCALANCE M812-1 ADSL-Router family (All versions < V8.1), SCALANCE M816-1 ADSL-Router family (All versions < V8.1), SCALANCE M826-2 SHDSL-Router (6GK5826-2AB00-2AB2) (All versions < V8.1), SCALANCE M874-2 (6GK5874-2AA00-2AA2) (All versions < V8.1), SCALANCE M874-3 (6GK5874-3AA00-2AA2) (All versions < V8.1), SCALANCE M874-3 3G-Router (CN) (6GK5874-3AA00-2FA2) (All versions < V8.1), SCALANCE M876-3 (6GK5876-3AA02-2BA2) (All versions < V8.1), SCALANCE M876-3 (ROK) (6GK5876-3AA02-2EA2) (All versions < V8.1), SCALANCE M876-4 (6GK5876-4AA10-2BA2) (All versions < V8.1), SCALANCE M876-4 (EU) (6GK5876-4AA00-2BA2) (All versions < V8.1), SCALANCE M876-4 (NAM) (6GK5876-4AA00-2DA2) (All versions < V8.1), SCALANCE MUM853-1 (A1) (6GK5853-2EA10-2AA1) (All versions < V8.1), SCALANCE MUM853-1 (B1) (6GK5853-2EA10-2BA1) (All versions < V8.1), SCALANCE MUM853-1 (EU) (6GK5853-2EA00-2DA1) (All versions < V8.1), SCALANCE MUM856-1 (A1) (6GK5856-2EA10-3AA1) (All versions < V8.1), SCALANCE MUM856-1 (B1) (6GK5856-2EA10-3BA1) (All versions < V8.1), SCALANCE MUM856-1 (CN) (6GK5856-2EA00-3FA1) (All versions < V8.1), SCALANCE MUM856-1 (EU) (6GK5856-2EA00-3DA1) (All versions < V8.1), SCALANCE MUM856-1 (RoW) (6GK5856-2EA00-3AA1) (All versions < V8.1), SCALANCE S615 EEC LAN-Router (6GK5615-0AA01-2AA2) (All versions < V8.1), SCALANCE S615 LAN-Router (6GK5615-0AA00-2AA2) (All versions < V8.1). Affected devices insert sensitive information about the generation of 2FA tokens into log files. This could allow an authenticated remote attacker to forge 2FA tokens of other users.

Weakness: CWE-532

Which versions are affected by CVE-2024-41978?

It affects 26 products.

Products include Siemens Ruggedcom Rm1224 Lte\(4g\) Eu Firmware, Siemens Ruggedcom Rm1224 Lte\(4g\) Nam Firmware, Siemens Scalance M804pb Firmware, Siemens Scalance M812-1 \(Annex A\) Firmware, Siemens Scalance M812-1 \(Annex B\) Firmware, Siemens Scalance M816-1 \(Annex A\) Firmware and 20 more.

How do I fix CVE-2024-41978?

No fix has been published for CVE-2024-41978 yet. Limit exposure of the affected software until one is available.

Is CVE-2024-41978 being exploited?

There is no known exploitation of CVE-2024-41978 in the wild and no public exploit code.

Sources

Also known as GHSA-9w3w-43cp-9hpg.

Is CVE-2024-41978 in your software?

Upload an SBOM and sbomify checks it against every vulnerability here, every day.