CVE-2025-40944 Denial of service in SIMATIC ET 200AL IM 157-1 PN
An attacker can cause a denial-of-service condition on Siemens SIMATIC I/O modules by sending a specific S7 protocol disconnect request, requiring a power cycle to recover.
- Exploited in the wild
- Not known
- Login needed
- Not needed
- Attackable
- Over the internet
- Victim action needed
- Not needed
- Fix
- None listed
What is CVE-2025-40944?
CVE-2025-40944 is a high-severity denial of service vulnerability in Siemens SIMATIC ET 200AL IM 157-1 PN, published on 13 Jan 2026. An attacker can exploit it over the internet without logging in, with no action from the victim.
Official description
A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0 < V4.2.5), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state. This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.
Weakness: CWE-400
Which versions are affected by CVE-2025-40944?
How do I fix CVE-2025-40944?
No fix has been published for CVE-2025-40944 yet. Limit exposure of the affected software until one is available.
Upgrade, then put limits on request size, rate and nesting depth so one client cannot exhaust the service. More about Denial of service.
Is CVE-2025-40944 being exploited?
There is no known exploitation of CVE-2025-40944 in the wild and no public exploit code.
Sources
Also known as GHSA-vqmm-3555-wq2q.