CVE-2026-13207 Frangoteam FUXA SCADA/HMI Authentication Bypass by Spoofing

High 8.7 Published Updated

Attackers can bypass authentication in FUXA SCADA/HMI to access sensitive user and role data via path normalization flaws.

Exploited in the wild
Not known
Login needed
Not needed
Attackable
Over the internet
Victim action needed
Not needed
Fix
None listed

What is CVE-2026-13207?

CVE-2026-13207 is a high-severity authentication bypass vulnerability in Frangoteam FUXA SCADA/HMI, published on 30 Jun 2026. An attacker can exploit it over the internet without logging in, with no action from the victim.

Official description

FUXA versions 1.3.1 and prior contain an authentication bypass vulnerability via dot-segment path normalization in the REST API. The API router fails to normalize dot-segment sequences before applying authentication middleware, allowing unauthenticated requests to access protected endpoints by prefixing paths with dot-segments such as /api/./users, /api/./roles, and /api/project/../users. These requests bypass authentication checks and return sensitive user and role data without credentials.

Weakness: CWE-290

Which versions are affected by CVE-2026-13207?

How do I fix CVE-2026-13207?

No fix has been published for CVE-2026-13207 yet. Limit exposure of the affected software until one is available.

Upgrade, and rotate credentials and sessions that may have been exposed. More about Authentication bypass.

Is CVE-2026-13207 being exploited?

There is no known exploitation of CVE-2026-13207 in the wild and no public exploit code.

Sources

Also known as GHSA-cgxf-x59w-2x25.

Is CVE-2026-13207 in your software?

Upload an SBOM and sbomify checks it against every vulnerability here, every day.

Check your SBOMs for free